PFC-3005T Obsolete Product

Conventional 5 Zone Fire Panel

Canadian Only

The PFC-3005T panel is designed for non-coded fire alarm systems in small commercial, institutional, and industrial occupancies. A slim-line design and a neutral beige exterior color offers an unobtrusive appearance to complement any interior.

The PFC-3005T includes one circuit board providing all the essentials for a complete fire alarm system. Five Class B initiating circuits and two Class B indicating circuits are provided by the PFC-3005T. The indicating circuit is protected from shorts by self-restoring circuitry.

Supervision includes ground fault detection, battery low level or open wire fault, initiating and indicating circuit wiring faults and loss of A.C. power. Initiating circuits are supervised for opens and ground faults. Indicating circuits are supervised for opens, shorts and ground faults. LED indicators are provided for Zone Alarm, Zone Trouble, A.C. On, Battery Fault, Ground Fault, Common Trouble, Signal Trouble and Signal Silenced. Switches are provided for Zone Disconnect/Silence, Trouble Silence and Reset.